AMS 3211-1500 COe In-Line

Complex combustion systems and processes require besides a fast in-situ O2 measurement to control the combustion, a quality measurement to adjust the combustion system at a level which avoids the generation of CO. The control level around the point of CO generation is the optimum of the combustion.

For this application AMS offers the flue gas probe AMS 3211-1500 with a dual sensor for the measurement of O2and unburnt combustibles (CO, H2 und hydrocarbons). The unburnt combustibles are measured as CO equivalent. Due to the fast response of the dual sensor both measuring values O2 and COe can be used for burner optimization.

The constuction of the flue gas probe AMS 3211-1500 is identical to the In-Line probe AMS 3211-500 with respect to the available dimensions and materials. The dual sensor is installed in the probe Tipp with ensures fast response. The operating temperature is up to 500 °C.

The dual sensor for the measurement of O2 and COe can be installed in any probe model of AMS.

Additional product features:

  • Immersion depth of 150 mm to 3000 mm
  • Probe tubes made of ceramic or Kanthal, depending on process temperature
  • Longer life expectancy of the ZrO2 sensor due to the reduced thermal load
  • Fast and easy sensor replacement
  • Flanges are available in DIN or ANSI sizes
  • Continuous monitoring of sensor signal, heater and measuring value on plausibility by the transmitter AMS 3220
  • Back-purge and auto-calibration features are available as options

Technical data

ZrO2 probeAMS 3211-1500
Measuring principleO2-COe-Sensor
ApplicationResidual oxygen in flue gas
ConstructionZO2-COe-Sensor installed in the tip of the probe
with stainless steel sinter metal filter screwed on
Flue gas temp., max.< 500 °C, short time to 550 °C
Dust content (flue gas)max. 5 grams / Nm3, if higher shield to protect against
abrasion or separate protecting tube
Flue gas velocitymax. 20 m/Sec., if higher shiled to protect against
abrasion or separate protecting tube
Time for pre-heating~ 10 Minutes
T90-Time< 10 Seconds
Reaction time< 2 Seconds
Probe length150 – 3000 mm
MaterialStainless steel 1.4541, Inconel 600
Installation in the stackpointing downward
Connecting flangesDN 65 PN 16, DN 80 PN 16 (larger on request)
ProtectionIP65
Reference air supplyby separate pneumatic unit
Calibration gas supplyby separate pneumatic unit
Weightca. 6,5 kg
Accessories 
TransmitterAMS 3220 in housing IP 65
Transmitter in twin-configuration
Pneumatic unitGRP housing, Dimensions: 800 x 600 x 300 mm
Back purge, Auto-calibration
Version: AMS 3211-1500 E V-2013-07